1.
Visible signals are now required in exit stairs.
Correct Answer
B. False
Explanation
NFPA 101, 2018, 9.6.3.5.5
2.
The latest published version of the Life Safety Code is ______.
Correct Answer
C. C. 2018
Explanation
The latest published version of the Life Safety Code is 2018.
3.
Fire detection, alarm and communications systems’ requirements are located in ______.
Correct Answer
B. B. Section 9.6
Explanation
The correct answer is B. Section 9.6. This section specifically addresses the requirements for fire detection, alarm, and communications systems. It is likely that this section provides detailed information and guidelines on the installation, maintenance, and standards for these systems.
4.
A fire alarm installed in accordance with the Life Safety Code must comply with the requirements of ______.
Correct Answer
C. C. Both A and B
Explanation
A fire alarm installed in accordance with the Life Safety Code must comply with the requirements of both NFPA 70 and NFPA 72. NFPA 70, also known as the National Electrical Code, provides guidelines for electrical installations, including fire alarm systems. NFPA 72, on the other hand, specifically focuses on the installation, testing, and maintenance of fire alarm systems. Therefore, in order to meet the requirements of the Life Safety Code, both sets of guidelines must be followed.
5.
When a fire alarm is impaired, procedures outlined in ______ shall be followed.
Correct Answer
B. B. NFPA 72
Explanation
NFPA 101, 2018, 9.6.1.5
6.
Smoke detectors shall not be located within ______ horizontal distance from a bathroom
Correct Answer
B. B. 36 in.
Explanation
NFPA 101, 2018, 9.6.2.10.6
7.
Visible signals are now required in elevators.
Correct Answer
B. False
Explanation
NFPA 101, 2018, 9.6.3.5.6
8.
Which of the following for generators is not required to be monitored by the fire alarm system?
Correct Answer
C. C. low gas
Explanation
The fire alarm system is designed to detect and alert in case of fire hazards. In the context of generators, monitoring the running status is important to ensure that the generator is functioning properly. Monitoring faults is crucial to identify any malfunctions or issues with the generator. Similarly, monitoring the position of the switch is necessary to ensure that the generator is in the correct mode of operation. However, monitoring low gas levels is not directly related to fire hazards and can be monitored separately by the generator system itself. Therefore, low gas is not required to be monitored by the fire alarm system.
9.
The provisions of section 9.6 shall apply to every other chapter of NFPA 101.
Correct Answer
B. False
Explanation
NFPA 101, 2018, 9.6.1.1
10.
When automatic smoke detection is required by Chapters 11 through 43, smoke alarms may be permitted to be used as an acceptable substitute.
Correct Answer
B. False
Explanation
Automatic smoke detection is required by Chapters 11 through 43, but smoke alarms may not be permitted as an acceptable substitute. Therefore, the correct answer is False.
11.
High rise buildings shall be equipped with an emergency voice communication/alarm system.
Correct Answer
A. True
Explanation
NFPA 101, 2018, 32.3.3.4.5
12.
Manual pull stations may be spaced at intervals not to exceed ______.
Correct Answer
D. D. 200 ft.
Explanation
Manual pull stations may be spaced at intervals not to exceed 200 ft. This means that there should be a manual pull station available within a maximum distance of 200 ft from any given point. This ensures that in case of an emergency, occupants can easily locate and activate a manual pull station to initiate the fire alarm system. Spacing the pull stations at appropriate intervals helps to ensure the prompt detection and notification of a fire, allowing for quick response and evacuation if necessary.
13.
When used in accordance with NFPA 72, emergency voice/alarm communication systems may be used for other purposes.
Correct Answer
A. True
Explanation
According to NFPA 72, emergency voice/alarm communication systems can be used for purposes other than emergency communication. This means that these systems can serve additional functions or be utilized in non-emergency situations as well.
14.
If a five-story building is protected by an automatic sprinkler system, the sprinkler system is permitted to be annunciated by the fire alarm system as a single zone.
Correct Answer
B. False
Explanation
NFPA 101, 2018, 9.6.7.4.5
15.
Manual fire alarm boxes must be all of the following except ______.
Correct Answer
A. A. red
Explanation
Manual fire alarm boxes must be visible, unobstructed, and accessible in order to ensure that they can be easily located and activated in case of a fire emergency. However, the color of the fire alarm boxes can vary depending on the building or jurisdiction. While red is a common color for fire alarm boxes, it is not a requirement, and they can be of any color as long as they meet the other criteria. Therefore, the correct answer is A. red.