The ProProfs editorial team is comprised of experienced subject matter experts. They've collectively created over 10,000 quizzes and lessons, serving over 100 million users. Our team includes in-house content moderators and subject matter experts, as well as a global network of rigorously trained contributors. All adhere to our comprehensive editorial guidelines, ensuring the delivery of high-quality content.
Learn about Our Editorial Process
| By Hugo Lopez
Hugo Lopez
Community Contributor
Quizzes Created: 6 | Total Attempts: 10,639
Questions: 45 | Attempts: 924

SettingsSettingsSettings
Planta Rural CD Mei 150---------by Cronos71 - Quiz

.


Questions and Answers
  • 1. 

    1. El rectificador  XR-50-50CR  cuenta con las siguientes protecciones:

    • A.

      Bobina de corte por alto voltaje, voltímetro y fusible de fusión a la salida.

    • B.

      Bobina de corte por alto voltaje, interruptor termo magnético de entrada y amperímetro.

    • C.

      Bobina de corte por alto voltaje, interruptor termomagnetico de entrada y fusible de fusión a la salida

    • D.

      Bobina de corte por alto voltaje, amperímetro y voltímetro.

    Correct Answer
    C. Bobina de corte por alto voltaje, interruptor termomagnetico de entrada y fusible de fusión a la salida
    Explanation
    The correct answer is "Bobina de corte por alto voltaje, interruptor termomagnético de entrada y fusible de fusión a la salida." This is because the rectificador XR-50-50CR has a high voltage cut-off coil, an input thermal magnetic switch, and a fuse for melting at the output.

    Rate this question:

  • 2. 

    El fusible de entrada del convertidor CVR 50 X es de un valor de: 

    • A.

      55 A

    • B.

      150 A

    • C.

      100 A

    • D.

      60 A

    Correct Answer
    B. 150 A
    Explanation
    The correct answer is 150 A because the input fuse of the CVR 50 X converter has a value of 150 A.

    Rate this question:

  • 3. 

    La función del Shunt de corriente en el tablero de fusibles de batería, es la de: 

    • A.

      Monitorear la corriente de batería

    • B.

      Monitorear la corriente de entrada

    • C.

      Monitorear el voltaje de salida

    • D.

      Monitorear el voltaje de batería

    Correct Answer
    A. Monitorear la corriente de batería
    Explanation
    The correct answer is "Monitorear la corriente de batería". The function of the Shunt de corriente in the battery fuse panel is to monitor the battery current. The shunt is a device that measures the current flowing through it by measuring the voltage drop across it. By monitoring the current, it helps to ensure that the battery is functioning properly and not being overloaded.

    Rate this question:

  • 4. 

    En la fuente interna, el elemento ____________ se alimenta de 12 V y proporciona 5 V regulados.

    • A.

      C32

    • B.

      CI9

    • C.

      C28

    • D.

      C21

    Correct Answer
    B. CI9
    Explanation
    CI9 is the correct answer because it is the component that receives 12 V from the internal source and regulates it to provide a stable 5 V output.

    Rate this question:

  • 5. 

    Potenciómetro para ajustar la limitación de corriente localizado en la tarjeta de control del rectificador XR 50-50

    • A.

      POT 3

    • B.

      POT 6

    • C.

      POT 5

    • D.

      POT 7

    Correct Answer
    A. POT 3
    Explanation
    POT 3 is the correct answer because it refers to a potentiometer located on the control card of the XR 50-50 rectifier. This potentiometer is used to adjust the current limitation.

    Rate this question:

  • 6. 

    Potenciómetro para ajustar la limitación de corriente localizado en la tarjeta de control del rectificador XR 50-50

    • A.

      Q8, Q9, Q10 y Q11

    • B.

      Q2, Q4, Q5 y Q6

    • C.

      Q1, Q3, Q5 y Q7

    • D.

      Q5, Q6, Q7 y Q8

    Correct Answer
    A. Q8, Q9, Q10 y Q11
    Explanation
    The correct answer is Q8, Q9, Q10, and Q11. These transistors are located on the control board of the XR 50-50 rectifier and are used to adjust the current limitation.

    Rate this question:

  • 7. 

    El fusible que se encarga de proteger a la celda contraelectromotriz y a los convertidores, cuya función es de 4+3 tipo eslabón, tiene una capacidad de:

    • A.

      300 Amperes

    • B.

      50 Amperes

    • C.

      200 Amperes

    • D.

      100 Amperes

    Correct Answer
    A. 300 Amperes
    Explanation
    The correct answer is 300 Amperes. The question mentions that the fuse is responsible for protecting the back electromotive force (contraelectromotriz) and the converters. It also states that the function of the fuse is of the 4+3 type. Based on this information, it can be inferred that a high capacity fuse is required to handle the power demands of both the contraelectromotriz and the converters. Therefore, the fuse needs to have a capacity of 300 Amperes.

    Rate this question:

  • 8. 

    La capacidad de los interruptores termo magnético, ubicados en el tablero de fusibles e interruptores de distribución tienen un valor de:

    • A.

      30 y 50 Amperes

    • B.

      10 y 30 Amperes

    • C.

      20 y 40 Amperes

    • D.

      40 y 60 Amperes

    Correct Answer
    A. 30 y 50 Amperes
    Explanation
    The correct answer is 30 y 50 Amperes. This is because the question is asking for the capacity of the thermal-magnetic switches located in the fuse and distribution switchboard. The given answer options provide different ranges of amperes, and the correct answer falls within the range of 30 to 50 Amperes.

    Rate this question:

  • 9. 

    Cuando el circuito tanque esta abierto, se presenta el siguiente caso en el rectificador:

    • A.

      El rectificador se dispara y toma mucha corriente

    • B.

      El rectificador se dispara y no toma corriente

    • C.

      El rectificador queda muy limitado

    • D.

      El rectificador no alcanza los niveles de tensión prefijados

    Correct Answer
    A. El rectificador se dispara y toma mucha corriente
    Explanation
    Cuando el circuito tanque está abierto, significa que no hay una carga conectada al rectificador. En esta situación, el rectificador no tiene una ruta para que la corriente fluya, lo que provoca que se dispare y tome mucha corriente. Esto se debe a que no hay una resistencia o carga que limite la cantidad de corriente que puede pasar a través del rectificador.

    Rate this question:

  • 10. 

    El diodo de transferencia exterior se localiza en:

    • A.

      El panel de entrada y salida del convertidor.

    • B.

      En la parte del bastidor de la planta de CD MEI 150

    • C.

      En el panel frontal del rectificador XR 50-50

    • D.

      En el panel frontal del convertidor CVR 100 X

    Correct Answer
    A. El panel de entrada y salida del convertidor.
    Explanation
    The correct answer is "El panel de entrada y salida del convertidor" which translates to "The input and output panel of the converter." This suggests that the exterior transfer diode is located on the panel where the input and output connections of the converter are made.

    Rate this question:

  • 11. 

    Potenciómetro para ajustar el Bajo Voltaje localizado en la tarjeta de control del rectificador XR 50-50.

    • A.

      POT 11

    • B.

      POT 2

    • C.

      POT 10

    • D.

      POT 8

    Correct Answer
    A. POT 11
    Explanation
    POT 11 is the correct answer because it is specifically mentioned in the given information that the potentiometer for adjusting the low voltage is located on the control card of the XR 50-50 rectifier. Therefore, POT 11 is the most likely option for adjusting the low voltage in this scenario.

    Rate this question:

  • 12. 

    Cuando ocurre un corte por alto voltaje, el rectificador XR 50-50-CR se restablece…

    • A.

      Con el botón de desbloqueo

    • B.

      Remotamente

    • C.

      Después de 10 seg.

    • D.

      Automáticamente

    Correct Answer
    A. Con el botón de desbloqueo
    Explanation
    El rectificador XR 50-50-CR se restablece con el botón de desbloqueo. Esto implica que cuando ocurre un corte por alto voltaje, se puede restablecer manualmente presionando el botón de desbloqueo en el rectificador. No se menciona ninguna otra forma de restablecimiento, como hacerlo de forma remota o de manera automática después de un cierto período de tiempo.

    Rate this question:

  • 13. 

    El oscilador y divisor de frecuencia, cuenta con un cristal de cuarzo (CY) de una frecuencia de _______, en el convertidor 50X.

    • A.

      15360 Hz

    • B.

      1680 Hz

    • C.

      1800 Hz

    • D.

      1450 Hz

    Correct Answer
    A. 15360 Hz
    Explanation
    The oscillator and frequency divider have a quartz crystal with a frequency of 15360 Hz in the 50X converter.

    Rate this question:

  • 14. 

    Potenciómetro que permite ajustar la alarma Bajo Voltaje, de la tarjeta rectificadora del convertidor CVR 50 X es:

    • A.

      POT 6

    • B.

      POT 4

    • C.

      POT 8

    • D.

      POT 2

    Correct Answer
    A. POT 6
    Explanation
    The correct answer is POT 6. The question is asking for the potentiometer that allows adjusting the Low Voltage alarm of the rectifier card of the CVR 50 X converter. Since the correct answer is POT 6, it can be inferred that this specific potentiometer is responsible for adjusting the low voltage alarm.

    Rate this question:

  • 15. 

    Para el ajuste de limite de corriente es necesario tener una carga:

    • A.

      Mayor o igual que 57 A

    • B.

      Igual a 46 A

    • C.

      Menor o igual que 45 A

    • D.

      Igual a 49 A

    Correct Answer
    A. Mayor o igual que 57 A
    Explanation
    In order to adjust the current limit, it is necessary to have a load that is equal to or greater than 57 A. This means that the load must be able to handle a current of at least 57 A without exceeding its capacity. If the load is less than 57 A, it may not be able to handle the current and could potentially be damaged. Therefore, the correct answer is that the load must be equal to or greater than 57 A.

    Rate this question:

  • 16. 

    La relación del shunt de corriente en el tablero de fusibles de batería, tiene un valor de:

    • A.

      300 Amperes / 50 mV

    • B.

      150 Amperes / 20 mV

    • C.

      200 Amperes / 50 mV

    • D.

      250 Amperes / 20 mV

    Correct Answer
    A. 300 Amperes / 50 mV
    Explanation
    The correct answer is 300 Amperes / 50 mV. This means that the shunt in the battery fuse panel has a resistance of 50 mV per 300 Amperes of current. The shunt is used to measure the current flowing through the circuit by measuring the voltage drop across it. In this case, a higher current will result in a higher voltage drop across the shunt.

    Rate this question:

  • 17. 

    Tablilla para conectar las alarmas del Convertidor CVR 50 X, localizada en el panel de Entrada y salida del convertidor:

    • A.

      TB1

    • B.

      TB3

    • C.

      TB2

    • D.

      TB4

    Correct Answer
    A. TB1
    Explanation
    The correct answer is TB1. This is because TB1 is the tablilla (terminal block) that is used to connect the alarms of the Convertidor CVR 50 X. It is located in the panel de Entrada y salida del convertidor.

    Rate this question:

  • 18. 

    La regulación de voltaje se garantiza dentro del ______ de vació hasta plena carga.

    • A.

      +- 1%

    • B.

      +- 3%

    • C.

      +- 4%

    • D.

      +- 2 %

    Correct Answer
    A. +- 1%
    Explanation
    La regulación de voltaje se garantiza dentro del rango de vacío hasta plena carga con una variación de +- 1%. Esto significa que el voltaje se mantendrá dentro de un margen de error del 1% tanto en condiciones de vacío como a plena carga. Esto asegura una estabilidad en el suministro de voltaje y evita fluctuaciones significativas que podrían afectar el funcionamiento de los dispositivos conectados.

    Rate this question:

  • 19. 

    La interconexión para la carga automática se encuentra en las terminales ________ de TB3.

    • A.

      9 y 10

    • B.

      11 y 12

    • C.

      5 y 6

    • D.

      7 y 8

    Correct Answer
    A. 9 y 10
    Explanation
    The correct answer is 9 y 10. The interconnection for automatic charging is located at terminals 9 and 10 of TB3.

    Rate this question:

  • 20. 

    La posición del interruptor de selección de régimen para obligar que la planta opere en régimen de igualación estando en condiciones normales es:

    • A.

      Manual

    • B.

      Automático

    • C.

      Apagado

    • D.

      Encendido

    Correct Answer
    A. Manual
    Explanation
    The correct answer is "Manual". In order to force the plant to operate in equalization mode under normal conditions, the position of the regime selection switch needs to be set to manual. This means that the operator will have to manually adjust and control the plant's operation to ensure equalization.

    Rate this question:

  • 21. 

    En el tablero los dos fusibles de batería tienen una capacidad de:

    • A.

      200 Amperes

    • B.

      50 Amperes

    • C.

      250 Amperes

    • D.

      100 Amperes

    Correct Answer
    A. 200 Amperes
    Explanation
    The correct answer is 200 Amperes. This is because the question states that "En el tablero los dos fusibles de batería tienen una capacidad de" which translates to "On the board, the two battery fuses have a capacity of." Therefore, the capacity of the two battery fuses is 200 Amperes.

    Rate this question:

  • 22. 

    El voltaje de flotación deberá ser ajustado a _______, mediante el potenciómetro 6, con el fusible de salida fuera

    • A.

      2.17 V/celda

    • B.

      2.12 V/celda

    • C.

      2.14 V/celda

    • D.

      2.20 V/celda

    Correct Answer
    A. 2.17 V/celda
    Explanation
    The correct answer is 2.17 V/celda. The voltage of a battery in a floating state should be adjusted to 2.17 volts per cell using potentiometer 6, with the output fuse disconnected.

    Rate this question:

  • 23. 

    Los rectificadores pasan automáticamente al estado de flotación, cuando el circuito de igualación automática…​​

    • A.

      Censa baja corriente

    • B.

      Detecta una sobre tensión

    • C.

      Censa alta corriente

    • D.

      Detecta baja tensión

    Correct Answer
    A. Censa baja corriente
    Explanation
    The correct answer is "Censa baja corriente" because rectifiers automatically switch to float mode when they detect a low current.

    Rate this question:

  • 24. 

    Potenciómetro para ajustar la alarma de Baja Corriente (carga mínima) localizado en la tarjeta de control del rectificador XR 50-50​

    • A.

      POT 2

    • B.

      POT 10

    • C.

      POT 8

    • D.

      POT 11

    Correct Answer
    A. POT 2
    Explanation
    The correct answer is POT 2 because it is the potentiometer specifically designed to adjust the low current alarm on the control card of the XR 50-50 rectifier. The other options (POT 10, POT 8, and POT 11) are not mentioned in the given information and therefore cannot be considered as the correct answer.

    Rate this question:

  • 25. 

    Cuando se tiene la configuración máxima en la plata CD MEI 150, la capacidad del fusible de salida después del convertidor es:

    • A.

      300 Amperes

    • B.

      100 Amperes

    • C.

      400 Amperes

    • D.

      200 Amperes

    Correct Answer
    A. 300 Amperes
    Explanation
    Cuando se tiene la configuración máxima en la plata CD MEI 150, la capacidad del fusible de salida después del convertidor es de 300 Amperes.

    Rate this question:

  • 26. 

    El fusible se encarga de proteger a la celda contraelectromotriz y a los convertidores, cuya función es 3+2 tipo eslabón, tiene una capacidad de:

    • A.

      200 Amperes

    • B.

      350 Amperes

    • C.

      300 Amperes

    • D.

      400 Amperes

    Correct Answer
    A. 200 Amperes
    Explanation
    The correct answer is 200 Amperes. A fuse is responsible for protecting the electromotive cell and converters. In this case, the fuse has a capacity of 200 Amperes.

    Rate this question:

  • 27. 

    Para una batería de 23 celdas, el ajuste de voltaje de igualación es de:

    • A.

      53.6 V. C. D.

    • B.

      52.5 V. C. D.

    • C.

      51.5 V. C. D.

    • D.

      50.0 V. C. D.

    Correct Answer
    A. 53.6 V. C. D.
  • 28. 

    Son dos de las partes básicas del convertidor CVR 50 X

    • A.

      Circuito inversor y circuito rectificador

    • B.

      Regulación de voltaje y regulación de corriente

    • C.

      Circuito de igualación y circuito de corte por alto voltaje

    • D.

      Circuito de reparto de carga y circuito tanque

    Correct Answer
    A. Circuito inversor y circuito rectificador
    Explanation
    The correct answer is "Circuito inversor y circuito rectificador". This answer is correct because the question asks for two basic parts of the CVR 50 X converter, and the circuito inversor (inverter circuit) and circuito rectificador (rectifier circuit) are two essential components of a converter. The inverter circuit is responsible for converting DC power into AC power, while the rectifier circuit converts AC power into DC power. Therefore, these two circuits are fundamental in the functioning of the CVR 50 X converter.

    Rate this question:

  • 29. 

    Tablilla de conexión de alarma localizada en el rectificador XR 50-50​

    • A.

      TB3

    • B.

      TB1

    • C.

      TB4

    • D.

      TB2

    Correct Answer
    A. TB3
    Explanation
    The correct answer is TB3 because it is the specific terminal on the XR 50-50 rectifier where the alarm connection board is located.

    Rate this question:

  • 30. 

    Potenciómetro que permite ajustar el nivel de ancho de pulso de convertidor CVR 50 X es:

    • A.

      POT 5

    • B.

      POT 7

    • C.

      POT 4

    • D.

      POT 3

    Correct Answer
    A. POT 5
    Explanation
    The correct answer is POT 5 because it is the potentiometer that allows adjusting the pulse width level of the CVR 50 X converter.

    Rate this question:

  • 31. 

    1. El puente de rectificación del rectificador XR 50-50, es a base de dos diodos de potencia de un valor de:

    • A.

      90 A

    • B.

      110 A

    • C.

      70 A

    • D.

      50 A

    Correct Answer
    A. 90 A
    Explanation
    The correct answer is 90 A. The rectification bridge of the XR 50-50 rectifier is based on two power diodes with a value of 90 A.

    Rate this question:

  • 32. 

    La capacidad del fusible de alarma para cada portafusiles, en el tablero de fusibles de batería es:

    • A.

      ¼ Ampere

    • B.

      ½ Ampere

    • C.

      4 Amperes

    • D.

      2 Amperes

    Correct Answer
    A. ¼ Ampere
    Explanation
    The correct answer is ¼ Ampere. The capacity of the alarm fuse for each fuse holder in the battery fuse panel is ¼ Ampere.

    Rate this question:

  • 33. 

    La función de la celda contraelectromotriz es:

    • A.

      Bajar el voltaje proveniente de rectificación

    • B.

      Quitar la alimentación a la carga

    • C.

      Contrarrestar el paso de corriente

    • D.

      Limitar a los convertidores

    Correct Answer
    A. Bajar el voltaje proveniente de rectificación
    Explanation
    La función de la celda contraelectromotriz es reducir el voltaje proveniente de la rectificación. Esto se logra mediante la generación de una fuerza electromotriz opuesta a la corriente que fluye desde la fuente de alimentación. Al hacerlo, la celda contraelectromotriz disminuye el voltaje y protege la carga de recibir un voltaje excesivo.

    Rate this question:

  • 34. 

    Potenciómetro para ajustar el Alto Voltaje localizado en la tarjeta de control del rectificador XR 50-50.

    • A.

      POT 10

    • B.

      POT 11

    • C.

      POT 8

    • D.

      POT 2

    Correct Answer
    A. POT 10
    Explanation
    The correct answer is POT 10 because it is the potentiometer specifically designed to adjust the high voltage on the control board of the XR 50-50 rectifier.

    Rate this question:

  • 35. 

    Potenciómetro para ajustar el Voltaje de flotación localizado en la tarjeta de control del rectificador XR 50-50.

    • A.

      POT 6

    • B.

      POT 4

    • C.

      POT 7

    • D.

      POT 3

    Correct Answer
    A. POT 6
    Explanation
    POT 6 is the correct answer because it refers to the potentiometer located on the control board of the XR 50-50 rectifier. This potentiometer is used to adjust the floating voltage.

    Rate this question:

  • 36. 

    Si se acciona el selector de normal/carga en el tablero de carga rápida en Telmex, los rectificadores se deben de ajustar a _________,  para 23 celdas

    • A.

      53.6 V. C. D.

    • B.

      53.2 V. C. D.

    • C.

      53.8 V. C. D.

    • D.

      54.3 V. C. D.

    Correct Answer
    A. 53.6 V. C. D.
    Explanation
    When the normal/charge selector is activated on the Telmex quick charge board, the rectifiers need to be adjusted to 53.6 V. C. D. for 23 cells.

    Rate this question:

  • 37. 

    Potenciómetro para ajustar el corte por alto voltaje localizado en la tarjeta de control del rectificador XR 50-50.

    • A.

      POT 11

    • B.

      POT 12

    • C.

      POT 10

    • D.

      POT 13

    Correct Answer
    B. POT 12
    Explanation
    The correct answer is POT 12 because it is mentioned in the given statement that the potentiometer for adjusting the high voltage cutoff is located on the control board of the XR 50-50 rectifier.

    Rate this question:

  • 38. 

    Potenciómetro que permite ajustar la alarma de Alto Voltaje, de la tarjeta rectificadora del convertidor CVR 50 X es:

    • A.

      POT 5

    • B.

      POT 2

    • C.

      POT 4

    • D.

      POT 3

    Correct Answer
    A. POT 5
    Explanation
    The correct answer is POT 5. This potentiometer allows the adjustment of the High Voltage alarm on the rectifier card of the CVR 50 X converter.

    Rate this question:

  • 39. 

    La función de la tarjeta 150-1EU, del tablero de fusibles e interruptores de distribución, es: 

    • A.

      Transmitir una señal negativa a la tarjeta 150-1DM

    • B.

      Adaptar la señal de entrada al filtro de salida.

    • C.

      Suavizar las pulsaciones a la salida del transformador.

    • D.

      Mantener constante la tensión de salida.

    Correct Answer
    A. Transmitir una señal negativa a la tarjeta 150-1DM
    Explanation
    The function of the 150-1EU card in the fuse and distribution switchboard is to transmit a negative signal to the 150-1DM card.

    Rate this question:

  • 40. 

    Potenciómetro para ajustar el voltaje de igualación localizado en la tarjeta de control del rectificador XR 50-50

    • A.

      POT 5

    • B.

      POT 6

    • C.

      POT 3

    • D.

      POT 7

    Correct Answer
    A. POT 5
    Explanation
    POT 5 is the correct answer because it is the potentiometer located on the control card of the XR 50-50 rectifier that is used to adjust the local voltage equalization.

    Rate this question:

  • 41. 

    Potenciómetro que permite ajustar la alarma de Corte por Bajo Voltaje, de la tarjeta inversora del convertidor CVR 50 X es:

    • A.

      POT 1

    • B.

      POT 3

    • C.

      POT 4

    • D.

      POT 2

    Correct Answer
    A. POT 1
    Explanation
    The correct answer is POT 1 because it is the potentiometer that allows adjusting the low voltage cut-off alarm of the CVR 50 X converter inverter card.

    Rate this question:

  • 42. 

    El valor del circuito limitador del corriente de salida del rectificador XR 50-50, es de:

    • A.

      55 A

    • B.

      52 A

    • C.

      48 A

    • D.

      50 A

    Correct Answer
    A. 55 A
    Explanation
    The correct answer is 55 A because the question is asking for the value of the output current limiting circuit of the XR 50-50 rectifier. The circuit is designed to limit the output current to 55 A.

    Rate this question:

  • 43. 

    Potenciómetro que permite ajustar la alarma de Corte por Alto Voltaje, de la tarjeta rectificadora del convertidor CVR 50 X es:

    • A.

      POT 4

    • B.

      POT 3

    • C.

      POT 1

    • D.

      POT 2

    Correct Answer
    A. POT 4
    Explanation
    The correct answer is POT 4 because it is stated that the potentiometer allows for adjusting the high voltage cutoff alarm of the rectifier card of the CVR 50 X converter. Therefore, POT 4 is the potentiometer that specifically serves this purpose.

    Rate this question: